In this article, we explain the factors that must be considered when selecting wire gauge of an electrical conductor. At the end, we suggest articles where the calculation is performed.
Choosing the correct wire gauge is essential to ensure electrical safety, efficiency, and compliance with the National Electrical Code (NEC). This tutorial provides a step-by-step guide to selecting the right wire size for your installation, following NEC standards.
1. Understand Wire Gauge and Its Role
- Wire Gauge (AWG): The American Wire Gauge (AWG) system determines wire size. Smaller AWG numbers correspond to larger wire diameters and higher current-carrying capacity.
- Importance: Proper wire sizing prevents overheating, voltage drop, and potential fire hazards.
2. Key Factors to Consider, selecting wire gauges
To select the right wire size, the following factors must be evaluated:
a. Ampacity
- Definition: The maximum current a wire can carry without exceeding its temperature rating.
- Reference: Use NEC Table 310.16 for ampacity ratings based on wire size, insulation type, and temperature rating.
- Example: For 60°C conductors (e.g., THW), a 12 AWG wire can handle 20 amps.
b. Voltage Drop
- Requirement: The NEC recommends a maximum of 3% voltage drop for branch circuits and a total of 5% for feeders and branch circuits combined.
- Increase the wire size if the voltage drop exceeds the recommended limits.
c. Length of Run
- Longer runs increase resistance, requiring a larger wire size to compensate for voltage drop.
d. Environmental Conditions
- Ambient Temperature: Higher temperatures reduce ampacity. Refer to Table 310.15(B)(1) for temperature correction factors.
- Conduit Fill: Multiple conductors in a conduit may require derating according to Table 310.15(C)(1).
e. Insulation Type
- Different insulation types, such as THHN, THW, and XHHW, have specific temperature ratings and ampacity values.
3. Steps to Select the Correct Wire Gauge
Step 1: Determine Circuit Load
- Identify the total load in amperes.
- Example: A 15-amp circuit for a general lighting load.
Step 2: Select Wire Type
- Choose wire insulation based on the environment and NEC requirements (e.g., THHN for dry locations, UF for underground).
Step 3: Use NEC Tables
- Refer to Table 310.16 to match the wire size to the circuit ampacity and insulation type.
- Example: For a 15-amp circuit using THHN wire in a dry location:
- A 14 AWG conductor is sufficient (rated for 20 amps).
Step 4: Check Voltage Drop
- Calculate voltage drop based on wire length. If it exceeds 3%, increase the wire size.
- Example: For a 120V circuit with a 100-foot run, 14 AWG may need to be upgraded to 12 AWG to mitigate voltage drop.
Step 5: Apply Adjustments
- Apply derating factors for temperature and conduit fill if applicable.
- Example: If the ambient temperature is 40°C and THHN wire is used:
- Apply a correction factor from Table 310.15(B)(1): Ampacity at 40°C = 90% of the listed value.
4. Quick Reference Table, selecting wire gauge
For copper conductors, at different temperatures. We show their most common use.
5. Common Applications
Residential Circuits
- 15 A circuits: Use 14 AWG wire.
- 20 A circuits: Use 12 AWG wire.
- 30 A circuits: Use 10 AWG wire.
Commercial Circuits
- 50 A equipment: Use 8 AWG or larger, depending on distance and voltage drop.
Special Considerations
- Motor Circuits: Refer to Article 430 for motor wire sizing, considering full-load current (FLC) and starting current.
- Service Entrance Conductors: Refer to Table 310.12 for residential services over 100 amps.
By following this guide and using NEC tables, you can confidently select the correct wire size for safe and compliant installations.
Always ensure your calculations align with the latest NEC standards and consult local codes for additional requirements.
For more information and tutorials, you can follow us on our Facebook page or visit this link under the electricity category.