In this article, we explain the smallest conductor sizes of copper and aluminum conductors permitted by the National Electrical Code (NEC), depending on their applications, the current they carry, and specific restrictions that apply.
This guide covers key aspects of conductor selection, including ampacity ratings and safety considerations, ensuring compliance with NEC standards. It is designed to provide a clear and practical understanding of the requirements for choosing appropriate conductors in various electrical installations.
Smallest conductor sizes
According to the NEC (National Electrical Code), the smallest conductor sizes for copper and aluminum are:
- Copper: The smallest allowable conductor size is 18 AWG for copper, which is typically used in low-power and control applications.
- Aluminum: The smallest allowable conductor size is 12 AWG for aluminum. Aluminum conductors are generally not manufactured or permitted in sizes smaller than 12 AWG because of their lower conductivity and mechanical properties compared to copper.
In many installations, especially for residential and commercial power distribution, copper conductors of 14 AWG are often the smallest allowed for branch circuit wiring due to ampacity requirements and NEC regulations (usually for 15-amp circuits).
The NEC provides several key guidelines and considerations for small conductors, including restrictions on their use, specific ampacity limits, and application contexts. Here’s what you should know:
1. Usage Restrictions on Small Conductors (NEC 240.4(D))
- The NEC sets limits on the maximum overcurrent protection for small conductors. Section 240.4(D) specifically restricts the overcurrent protection for small conductors based on their gauge:
- 18 AWG: Max protection of 7 amps.
- 16 AWG: Max protection of 10 amps.
- 14 AWG Copper: Typically protected by a 15-amp breaker for most branch circuits.
- These restrictions are intended to prevent overheating and ensure safe operating conditions. The smaller the gauge, the more vulnerable the conductor is to overheating under high loads.
2. Applications of Small Conductor sizes (Control and Signaling Circuits)
- Control Circuits: Small conductors, such as 18 AWG and 16 AWG, are often used in low-voltage control and signal applications rather than for power distribution.
- Signaling and Communication: In systems like telecommunications, alarms, and low-power lighting, these small-gauge conductors are common due to their low current requirements and shorter circuit distances.
- The NEC allows 18 and 16 AWG for these specialized circuits as they typically carry low currents and are less likely to overheat.
3. Small Conductor Ampacity Tables
- The NEC ampacity tables (Table 310.16) provide ampacity limits for various conductor types, insulation ratings, and ambient temperature adjustments. For example:
- 14 AWG Copper: 20 amps at 90°C insulation, but often limited to 15 amps by NEC for branch circuits.
- 18 AWG Copper: 14 amps (with appropriate insulation), but limited to 7 amps per NEC 240.4(D).
- Insulation Rating: The ampacity of small conductors depends on the insulation rating (e.g., 60°C, 75°C, 90°C). For example, THHN (90°C insulation) allows for higher ampacity than TW (60°C insulation).
4. Voltage Drop Considerations for Small Conductors sizes
- Due to their higher resistance, small-gauge conductors experience a more significant voltage drop over long distances. The NEC recommends limiting voltage drop to 3% for branch circuits and 5% for the entire circuit to maintain efficient operation.
- For this reason, small conductors are generally limited to short runs in low-power applications to avoid excessive voltage drop and power loss.
5. Grounding Conductors (NEC 250)
- In grounding systems, small conductors like 16 and 18 AWG are sometimes used in low-voltage, low-current grounding applications. However, the NEC restricts these conductors in higher-current applications due to their limited ampacity.
- Section 250.122 outlines grounding conductor sizes, with minimum sizes based on circuit ampacity to ensure that the grounding system can safely carry fault current.
6. Environmental and Thermal Conditions (NEC 310.10)
- Small conductors are sensitive to environmental factors, especially heat. NEC section 310.10 addresses adjustments to ampacity based on ambient temperatures and conditions like bundling or conduit fill, which can reduce heat dissipation and increase conductor temperature.
- Temperature Derating: When installed in high-temperature environments or in conduit with multiple conductors, small conductors must be derated, meaning they carry less current to prevent overheating.
7. Flexible Cords and Fixture Wires (Article 400)
- Small conductors are commonly used in flexible cords and fixture wires, where 18 AWG or 16 AWG wires are often used for their flexibility and ease of installation.
- NEC Article 400 regulates the use of flexible cords and specifies where small conductors may be used, such as in pendant lights, appliances, and portable equipment. These cords must meet specific NEC standards for insulation and construction.
Summary:
- Protection Limitations: Small conductors have strict overcurrent protection limits (7A for 18 AWG, 10A for 16 AWG).
- Application Restrictions: Limited mainly to control, signaling, and low-power applications.
- Voltage Drop: Small conductors are suitable only for short distances due to higher resistance.
- Environmental Adjustments: Ampacity may need to be reduced in high-temperature or bundled conditions.
- Grounding Limitations: Small conductors are restricted in high-current grounding due to low ampacity.
These NEC guidelines ensure that small conductors are used safely and effectively within their capacity limits, preventing hazards like overheating and insulation failure.